Freezer Floor

Frost Heave Prevention System:

Heating System shall consist of Self-regulating cable mounted in rigid conduit below the insulation in the Mud Slab or aggregate. System shall be controlled and monitored by a processor based controller that Controls, Monitors, Alarms, and provides troubleshooting information as standard design.

1)     System Provider:

a.      System provider shall be experienced in Frost Heave Prevention System with over 35 years’ experience in design, installation, startup and troubleshooting.

b.      Provide detailed Layout drawings

c.      Provide Electrical details and electrical drawings.

d.      Provide Complete installation and startup instructions.

e.      Provide replacements parts list with standard off the shelf replacement part numbers.

f.       Provide a Detailed Check Out form for startup.

g.      Provide a 2 year warranty on the Control system.

h.      Provide a 1 year warranty on the Heat Cable.

i.       Acceptable manufactures Thermal Equipment Sales Co. Inc. Memphis Tn. 901-452-4516

 

2)     Floor Heating Cable:

a.      Cable shall be Self-regulating Low temperature cable, wattage rating per spec.

b.      Cable shall operate at an equilibrium temperature of 50º F at the rated wattage and regulate temperature all along the entire length. 

c.      Construction:

                                                    i.     industrial grade 16AWG buss wire

                                                   ii.     tinned copper braid for a grounding conductor

                                                  iii.     Fluoropolymer over-jacketing, ensuring operating integrity for corrosive and heavy moisture laden industrial environments.

                                                  iv.     Heating cable should have a maximum maintenance temperature rating of 150°F (65°C).

                                                   v.     UL Listed for ordinary areas and fire protection system piping.

                                                  vi.     FM Approved for ordinary and hazardous areas

                                                vii.     Maximum circuit lengths shall be calculated at 32º F

d.      Terminations:

                                                    i.     Shall be made with Silicone End Power Connection kits on both ends of cable

                                                   ii.     Tinned copper overjacket shall be grounded per code

                                                  iii.     The heating cable shall be supplied with a High temperature Silicone sealant, to provide a moisture seal where the Cable penetrates the junction box.

                                                  iv.     Junction Termination box shall be a Metal Weather Proof Enclosure(s) with screw cover that has 4” square minimum dimensions. Provided by others.

 

 

 

 

3)     Processor based Floor Monitor and Control System shall Monitor, Control and Alarm all facets of the Frost Heave protection system.

a.      Control System shall operate Heat Trace Cable at a user determined design temperature (minimum setpoint 32ºF).  Control setpoint and temperature alarm are field accessible. 

                                                    i.     Summer Peak Utility control input shall cycle the design temperature to provide a lower heat output during peak operating times. Provided by a user supplied remote digital input (24 VDC).

                                                   ii.     Hardware

1.      Modicon PLC 40 I/O with Thermocouple input module

2.      256 kB memory internal RAM

3.      Battery Backup (standard over the shelf battery replacement)

4.      Internal Data backup 256 kB built-in flash memory backup of application and data

5.      2 GB SD card (optional) 

6.      USB port

7.      Ethernet port and Modbus ports

8.      GFI Circuit protection (all circuit protection shall be rated for inrush current)

9.      Monitor GFI breakers for Personal and Equipment safety 40 amp 30 mA

10.   Branch circuit protection, Supplementary Protectors Class UL1077

11.   Solid State relays rated for inrush current

12.   Main Disconnect with Lock out / Tag out Door interlocking mechanism

13.   Control transformer fused primary and secondary protection

14.   Low voltage power supply rated at 60 watts 24 volts

15.   5.7” Color HMI Monitor shall be rated NEMA 4X for indoor wet and corrosive environments

16.   NEMA 12 Enclosure

                                                  iii.     Monitoring shall include fault history for each variable, with troubleshooting tips, and replacement part numbers for specific installation.  Each alarm shall clearly indicate the location and circuit affected.

1.      Temperature, with low temperature alarm, per Circuit

2.      GFI for ground fault conditions

3.      Branch Circuit fault conditions

4.      End of run monitor for Continuity

5.      Thermocouple Lead break protection

                                                  iv.     Alarm Outputs

1.      Alarm output 24 Volt DC for user DCS System or external monitoring

2.      Ethernet connection for Remote monitoring

3.      Timed monitoring of system Circuits in temperature alarm conditions

4.      Sensor lead break protection

5.      90 DB Alarm Horn shall have an alarm silence push button and 24 hour restart until system fault(s) are corrected.

6.      Flashing Red Beacon indicates Alarm Conditions

                                                   v.     Control system shall come complete and pretested for easy field startup with all control outputs and inputs terminated at clearly labeled terminal strips.

4)     Installation:

                                                    i.     Install electric heating cable according to the drawings and the manufacturer’s   instructions. 

                                                   ii.     The installer shall be responsible for providing a complete functional system, installed in accordance with applicable national and local requirements. 

                                                  iii.     Grounding of controller shall be performed according to Section 26 05 26            "Grounding and Bonding for Electrical” 

                                                  iv.     INSTALLATION TESTING

1.      When the heater cable and connections for a circuit have been completed, immediately perform the following checks: 

a.      Visually inspect the heater cable. If damage is seen, either replace the complete heater cable, or cut out the damaged section. (no splices shall be made in conduit)

b.      Inspect all connections to be sure they are correctly assembled. Be sure each heater cable entry to a connection has a moisture resistant seal and caps are properly installed.

c.      Inspect the insulation resistance of the circuit using a 500VDC megger. Always perform this test at the power connection. Any cable with an insulation resistance of less for than 10 megohms should be removed and discarded.

d.      Check voltage at end of circuit and record in log on the Detailed Check-out Form. Systems with End of run continuity monitoring check for relay operation when energized.  Check amperage and on each cable at startup and again in 30 minutes, record amperage for future Preventive maintenance checks.  Verify all alarms are engaged as per Checkout form.