Freezer Floor Systems Frost heave prevention for freezer and cold storage floors
(901) 452-4516 A division of Thermal Equipment Sales Co., Inc. AboutContactRep Login

Sheet 04 · Controls

Controls and monitoring

A frost heave system can fail quietly. The ground cools slowly, and by the time the floor moves the soil may be frozen deep. The controls have to find a failed circuit in hours, not after a season.

01What the controls must catch

Older heat cable controls watched current draw. That works for constant-wattage cable, where a healthy circuit draws a known current. Self-regulating cable draws different current as its temperature changes, so current alone cannot tell a healthy circuit from a damaged one.

Our panels confirm operation directly at the far end of each run and back it up with ground temperature:

  • Continuity monitor, per cable run. Voltage from the far end of each run energizes an end-of-run relay in the panel. Voltage present when the PLC calls for heat proves the breaker, solid-state relay, ground-fault breaker and that run are all passing power; losing it is an end-of-run alarm that names the circuit and run. Voltage present when the PLC is not calling for heat means a relay has failed shorted.
  • Ground-fault and breaker status, per circuit. Auxiliary contacts on each breaker report a trip.
  • Ground temperature, per zone. An independent check that does not rely on any electrical reading, with a low-temperature alarm and a thermocouple break alarm.
Touchscreen titled Freezer Floor Control / Alarm showing set floor temperature and eight zone temperatures with heat on or off status
Fig. 1Operator screen: set floor temperature, zone temperatures and heat status for eight zones.

02System architecture

Control and monitoring block diagramBuilding connections at the top, the control panel in the middle and the freezer floor at the bottom. Single-source incoming power passes through a lockable main disconnect to a 24 VDC power supply for the PLC, and to a breaker, solid-state relay and 30 mA ground-fault (GFEP) breaker for each circuit; the heat cable is connected at the GFEP breaker. Breaker and ground-fault status, a continuity monitor (far-end voltage of each run on end-of-run relays), and the thermocouples all report to the PLC, which drives the touchscreen, horn and beacon and connects to the building management system, a utility peak-setback signal and optional Ethernet/Modbus.BUILDINGCONTROL PANELFREEZER FLOORIncoming powersingle source powerBMS / alarm systemdry contact / 24 VDCUtility peak signalremote inputEthernet / ModbusoptionalMain disconnectlockable (LOTO)24 VDC power supplyfusedPLC + thermocouple inputssetpoint · alarms · fault log · timersColor touchscreenstatus · historyHorn + red beaconsilence push buttonBreakerper circuitSSRper circuitGFEP 30 mAper circuitheat cable lands hereContinuity monitorfar-end voltage, per runend-of-run relays× ONE SET PER HEATING CIRCUITHeat cable loopsself-regulating, in rigid conduitThermocouplesType J, one per zoneon / offalarm outsetbackbreaker / GFEP statusfar end of each runcontinuity / voltageground temp.power / controlmonitoring signalheating circuitground temperature
Fig. 2Control and monitoring block diagram, building to floor. Each heating circuit has its own breaker, solid-state relay and 30 mA ground-fault (GFEP) breaker, where the heat cable is connected. Breaker and GFEP status, the continuity monitor and the zone thermocouples all report to the PLC.

03Monitored points

PointDetectsOperator sees
Ground temperatureZone below setpoint or below the low alarm limitZone temperature, heat on/off, low-temperature alarm and total time spent in alarm
Thermocouple circuitOpen or broken sensor leadSensor fault alarm with zone
Continuity monitor (far-end voltage)Open cable run; relay failed open; breaker or ground-fault breaker off; relay failed shortedEnd-of-run alarm with circuit and run number
Ground-fault breakerGround-fault or overcurrent tripBreaker fault with circuit number
Fault historyEvery event, with count per conditionLog with location, time in fault, troubleshooting steps and replacement part numbers

04Alarms and remote monitoring

05Temperature control

A PLC with thermocouple inputs holds each zone at a user-set temperature, which cannot be set below 32 °F. Each circuit is switched by a solid-state relay rated for heat cable inrush. Self-regulating cable already reduces its own output as the base warms; the controller switches it off entirely when the zone is at setpoint, which saves energy and reduces cable temperature cycling.

Peak setback. A remote 24 VDC input lowers the setpoint during utility peak-demand periods. The ground has enough thermal mass that a few hours of reduced heat do not affect it.

06Electrical protection

Main disconnectDoor-interlocked, lockable for lockout/tagout
Branch protectionDedicated breaker for each circuit, C-curve or otherwise rated for self-regulating cable inrush
Ground-fault protection30 mA ground-fault equipment protection on every heating circuit, with auxiliary contact to the PLC
Control powerFused 24 VDC power supply
WiringPre-wired and tested at our shop; all field connections on labeled terminal strips; main lugs for incoming power

07Enclosures and panel photos

Panels are built in NEMA 12, 3R, 4 or 4X enclosures to suit the location, including NEMA 4X fiberglass and NEMA 4X stainless steel for food processing and washdown areas. Standard panels handle up to 5 circuits and 15 cable runs; larger panels have been built for up to 36 circuits and 72 runs.

FFCH freezer floor monitor and control data sheet (PDF)